The GPIO connector is Micro-Fit 3.0™ 2 x 7 position 3.0 mm pitch connector manufactured by Molex

(http://www.molex.com) .

Digital inputs have pull-down resistors. All general purpose I/O (GPIO) pins (i.e. all input and outputs) have transient protection.

 The I/O port provides for the control of 4 external devices and for monitoring 4 external inputs.

GPIO Block Pin

Signal

Name

1

INPUT1

Single Ended Input 1

2

INPUT2

Single Ended Input 2

3

INPUT3

Single Ended Input 3

4

INPUT4

Single Ended Input 4

5

VCC

Power (Power supply output – fused)

6

RS485

Negative

7

RS232

RxD

8

DOUT1

Output 1

9

DOUT2

Output 2

10

DOUT3

Output 3

11

DOUT4

Output 4

12

GND

Common Ground for Power

13

RS485

Positive

14

RS232

TxD

GPIO Output Connection

The 4 outputs are configured as "open drain," enabling direct connection “open drain” which means that they can be directly connected to energize external relays, lamps, or other DC devices.

The maximum  Maximum supply voltage is 36 volts, with a maximum load current of 500mA.

It is recommended to use  Recommended wire gauge for use with the connector is 20-24 AWG wire gauge with the connector. Please note . Note that the OUT GND connection is linked connected to the CTM-500's ONE’s supply ground.

image-20240328-181443.pngImage Removedoutput connection.pngImage Added

GPIO Input Connection

The 4 inputs on may be configured in the CTM-500 can be configured ONE for monitoring either a digital DC voltage state or an analog DC voltage. All of the inputs are single - ended.

For digital state monitoring, the minimum input voltage range is 0 -volts while the maximum is 36 volts.

The threshold detection voltage is set at 2.5 volts with 1 volt of hysteresis. Please note Note that the IN GND connection is referenced to the CTM-500’s ONE’s supply ground.

Analog  Analog input values are will be sampled and can be reported at a maximum frequency of 10Hz.

Example of Digital Input wiring

image-20240328-181634.pngImage Removeddigital input.pngImage Added

For analog voltage monitoring , the measurement range is 0 to +10 volts with a 10mV resolution of 10mV. The input can tolerate voltages withstand up to 36 volts. Please note Note that the IN GND connection is referenced to the CTM-500’s ONE’s supply ground.

Example of Single Ended Analog Input Wiring

...

input wiring.pngImage Added